ABB

SafeRing/SafePlus 24kV

01 Side connected metering. Measuring voltage on the cable-in side
This solution is non-arc proof only. Installation on the base frame is not possible.
Click Here
SafePlus combined with SafeRing
which is ABB’s standard ring main unit, represents a complete solution for 12/24 kV distribution networks
Click Here
Previous slide
Next slide

Gas-insulated compact switchgear, SafePlus

Medium voltage (MV) compact SF6-insulated switchgear for secondary distribution up to 40.5 kV, 630A

SafePlus is a metal enclosed compact switchgear system for distribution applications up to 40.5 kV. The switchgear has a unique flexibility due to its extendibility and the possible combination of fully modular and semi-modular configurations. SafePlus is from the same product family as SafeRing and has identical user interface.

SafePlus is a completely sealed system with a stainless steel tank containing all live parts and switching functions. A sealed steel tank with constant atmospheric conditions ensures a high level of reliability as well as personnel safety and a virtually maintenance-free system.

ABB Gas-insulated compact switchgear SafePlus

Product scope

  • 12-24 kV, 630A
  • 36-40.5 kV, 630A

Key features

  • Minimal maintenance
  • No live parts exposed
  • One full range up to 40.5 kV
  • Module width: 325mm for 12-24kV, 420mm 36kV
  • Optional arc suppressor: No gases released even in arc fault cases
  • Optional fully modular switchgear

Operation of vacuum circuit-breaker

The isolator in the V-module can only be opened after the circuit-breaker is opened. Then the circuit-breaker can be closed for testing purposes.

Mechanical position indicators:
Mechanical position indicators
  • Green push-button closes the switch A
  • Red push-button opens the switch B
  • Mechanical position indication, circuit-breaker open C
  • Mechanical position indication, earthing switch closed D
Vacuum circuit-breaker:
Vacuum circuit-breaker
  • Charging springs: Turn the operating handle clockwise to charge the closing and the opening spring
  • Close: Push the green button A
  • Open: Push the red button B
Switch disconnector:
Switch disconnector
  • Close: Turn the operating handle clockwise.
  • Open: Turn the operating handle anti-clockwise.
 
Earthing switch:
Earthing switch
  • Close: Turn the operating handle clockwise.
  • Open: Turn the operating handle anti-clockwise.
  • Don’t hesitate to contact us for more details and to learn more information.